Home
Product Catalog
News
Contact Us

Product Catalog 

4/816 zones conventional fire alarm control panel

  • 4/816 zones conventional fire alarm control panel
  • 4/816 zones conventional fire alarm control panel
  • 4/816 zones conventional fire alarm control panel
  • 4/816 zones conventional fire alarm control panel
Model No.︰zc1016/4/8
Brand Name︰zoanco
Country of Origin︰China
Unit Price︰US $ 229 / pc
Minimum Order︰1 pc
Share on:

 Total 20 Related Items 
12345Next

Product Description

Conventional fire alarm control panel is available for 4zones,8zones and 16zones

Product Description 

The PANEL is a 4-zone to 16-zone FACP (Fire Alarm Control Panel), which uses conventional input devices.  The panel accepts water flow devices, two-wire smoke detectors, four-wire smoke detectors, pull stations and other normally-open contact devices. Outputs include four Notification Appliance Circuits (NAC, SOUND1-4), three standard Form-A relays (alarm, trouble and supervisory) and an EIA-485 port to interface with remote annunciators and optional remote relay modules. The FACP is field programmable via the panel keypad.  It also supervises all wiring, AC voltage and battery level.

 

This series of panels are basically the same in application and operation, their differences are shown in Table 1-1. PANEL will be described as the example in the following sections.

 

Table 1-1

FACP

Number of Detection Zones

Number of Sounder Outputs

Output Delay Settings

PANEL-4

4

1

N/A

PANEL-8

8

2

N/A

PANEL-16

16

4

N/A

 

1.1 ProductFeatures

 

4,8,16 Class B Initiating Device Circuits (IDCs)

   All zones accept conventional detectors and any normally open contact device

Four Class B Notification Appliance Circuits (NACs)

One Form-A Alarm Relay

One Form-A Trouble Relay

One Form-A Supervisory Relay

3.0 amps of system power

Max 20 conventional detectors in one zone.

Auto/Manual mode setting enable walk test.

Each Zone can be disabled,

Sound output can be disabled.

Manual active sound output enabled.

Able to report short and broken circuit of detection zones.

Designed with standby batteries and space provision for two sealed lead-acid batteries.

Testing and disable functions.

Can connect max 32 repeater panels by RS485 communicaiton port

 

 

1.2 Specifications

 

AC Power

90-270 VAC, 50 Hz, 2.3 amps

Wire size: minimum #14 AWG (2.0 mm2) with 600V insulation

Battery (lead acid only)

Maximum Charging Circuit: Normal Flat Charge—27.6V @ 0.8 amp

Maximum Charger Capacity: 18 Amp Hour batter

Sound Output Device Circuits

General Alarm Zones 1 through 16

Operation: All zones Class B

Normal Operating Voltage: Nominal 24 VDC (ripple = 100 mV maximum)

Alarm Current: 15 mA threshold

Short Circuit Current: 42 mA maximum

Maximum Loop Resistance: 100 ohms

End-of-Line Resistor: 4.7K, ½ watt

Detector Loop Current is sufficient to ensure operation of two alarmed detectors per zone

Standby Current: 7.26 mA

Three Relays Output

Relay contact rating: 2.0 amps @ 30 VDC (resistive), 2.0 amps @ 30 VAC (resistive)

Nonresettable 24 VDC Power

Maximum ripple voltage: 10 mVRMS          Operating Voltage nominal 24 volts

Total DC current available from this output is up to 500 mA

Recommended maximum Standby current is 150 mA

Payment Terms︰TT/L
Product Image





Related Products
AC 90-270v Powered Gas Alarm lpg Gas detector  LPG Gas Alarm
AC 90-270v Powered Gas Alarm lpg Gas detector LPG Gas Alarm
US $ 9.9
Addressable  fire alarm control panel   intelligent FACP
Addressable fire alarm control panel intelligent FACP
US $ 799
Optical beam smoke detector Conventional Reflective Beam Detector  smoke alarm
Optical beam smoke detector Conventional Reflective Beam Detector smoke alarm
US $ 199
Addressable manual call point used with an intelligent two-bus control panel
Addressable manual call point used with an intelligent two-bus control panel
US $ 12




Home  |  Product Catalog  |  News  |  Contact Us  |  Sitemap  |  Mobile Version
  English     简体版     繁體版

Powered by DIYTrade.com  Build your FREE website !