Mini conventional 2zones fire alarm control panel
Product Features
2 conventional input zones
1 notification appliance circuits(NAC) with bult-in synchronization for ANSI3.41 and Gentex.
The panel comes with a 2 amp power supply
Dedicated alarm and trouble relays
1 RS485 can be able to connect the other panel
Housed in a 205mm Wx258mm Hx81mm D metal enclosure
Enclosure supports two 12V,4Ah backup batteries
Electrical specifications
Primary AC: 120VAC 50/60Hz power supply rating,240VAC 50/60Hz
Power supply rating: 2amps@24VDC
Maximum battery charing current: 0.98amps@26VDC
Initiating Device circuits 2 zones: Alarm zone 2
Normal initiating operating voltage: 23VDC,Maximum 26VDC,regulated
Normal quiescent current(normal status): <50mA
Alarm current(not include the others): <150mA
short circuit initiating current ( perzone): 35mA maximum
Maximum initiating resistance ( per zone): 10 ohms
initiating End-of-line Resistor: 4K7 ohms,1/2W 5%
Standby Detector Current(per zone): 4mA maximum
Maximum Detector Count(per zone): 30detectors
Initiating Cabling Type: 18AWG Twisted Shielded pair(14-18AWG)
Detector base impedance: 430ohms
Notification Appliance Circuits: 1NACs,special application
Maximum NAC current Rating: 1Amp maximum per circuit
NAC operating voltage: 26VDC Nominal,30VDC Maximum
NAC End-of-line resistor: 1N4007 Diode
FAULT Relay rating: 2A&30VAC, resistive
Alarm(Auxiliary)Relay rating: 2A&30VAC,resistive
CP1002M(Master alarm panel): with power supply and digital display
CP1002S(Slave alarm panel): with power supply,without digital display.